Climatic test


Devices and components determined for outside operation, have to function faultlessly even under extreme climatic conditions. Under these circumstances, power supply is extremely important. A test in our climatic chamber reveals, whether or not all necessary variables have been considered in the construction process. A variety of conditions can be simulated here.

Amongst others:
Temperature cycle testings under mechanical strain on:
- Composite isolators according to IEC 61109
- Composite housed isolators to IEC 61462
- Metal oxyde surge arresters according to IEC 60099-4
Testing of the correct operation of disconnectors under icing conditions, according to IEC 60694.
Testing according to manufacturer's specifications, within the framework of the technical data.

Climatic chamber size
6m x 4m x 4,5m (LxWxH)

Test conditions
Temperature: -30°C to +50°C
Cooling capacity: 1,720 kJ/h
Humidity: Above +10°C, relative humidity adjustable from
20% to 90%
Power-frequency voltage up to 300 kV
Direct voltage up to 400 kV





Temperature cycle test with
mechanical loading on a
composite housed isolator